This XPSABV safety module monitors emergency shutdown pushbuttons and limit switches. It meets the requirements of PL e/Category 4 (instantaneous safety outputs), PL d/Category 3 (time delayed safety outputs) conforming to EN/ISO 13849-1. It meets also the requirements of SILCL3 (instantaneous safety outputs) and SILCL2 (time delayed safety outputs) conforming to EN/IEC 61508 and EN/IEC 62061. It can be used for monitoring Emergency stop circuits conforming to EN/ISO 13850 and EN/IEC 60204-1 standards, and electrical monitoring of switches in protection devices conforming to EN/ISO 14119 standard. It has removable terminals for easier and better control wires tightening, thus improving installation reliability.