{"product_id":"17-25a-cl-20-therm-olr-everlink-sch-lrd325l","title":"17-25A CL 20 therm. OLR \/ Everlink","description":"TeSys LRD thermal overload relay, 25A\/690V, thermal setting range 17-25A, tripping class 20, for protection of 3-phase motors 11kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by EverLink BTR screw terminals , it connects directly to the bottom terminals of 3-pole contactors LC1D40A-D80A. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LAD96560 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHs\/Reach).","brand":"Schneider Electric","offers":[{"title":"Default Title","offer_id":42865157701721,"sku":"SCH-LRD325L","price":0.0,"currency_code":"CAD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0601\/1171\/6441\/files\/LRD325L_1_20-_2049310a0b-a384-436b-bb7f-3b8721ebdc7d.jpg?v=1764018790","url":"https:\/\/www.guillevin.com\/products\/17-25a-cl-20-therm-olr-everlink-sch-lrd325l","provider":"Guillevin","version":"1.0","type":"link"}