{"product_id":"adv-cntrl-unit-cl20-3ph-0-15-0-6a-110-240vac-sch-lucdx6fu","title":"UNITE 0,15-0,6A 110-240V  CTRL EVOLUTIF","description":"TeSys U control and diagnostic unit to be inserted in advanced power bases LUB120, LUB320, LUB380 to form a TeSys U starter controller, for 3-phase motor applications up to 0.09kW@400V. It provides full protection to motors with a rated current Ir 0.15-0.6A (Ir adjustable), overload tripping class 20, short circuit at 13 x Irmax, overcurrent at 14.2 x Ir, phase loss, insulation fault (protection of equipment only). For diagnostics, it provides a thermal overload alarm to be managed with an additional function module (to be ordered separately) and a test push button for overload simulation. To be used with a 110-240V AC \/ 110-220V DC voltage for the control of the starter (through the control terminals A1\/A2 located in the power base). Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS\/REACh).","brand":"Schneider Electric","offers":[{"title":"Default Title","offer_id":42866291441753,"sku":"SCH-LUCDX6FU","price":0.0,"currency_code":"CAD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0601\/1171\/6441\/files\/LUCDX6FU_1_20-_20149dc461-00bd-49b8-b22d-e24513c336d5.jpg?v=1764021418","url":"https:\/\/www.guillevin.com\/fr\/products\/unite-0-15-0-6a-110-240v-ctrl-evolutif-sch-lucdx6fu","provider":"Guillevin","version":"1.0","type":"link"}